ColdLogik CL80 60kw data center InRow Coolers
  • ColdLogik CL80 60kw data center InRow Coolers

ColdLogik CL80 60kw data center InRow Coolers

$16,647.00

ColdLogik CL80 InRow Coolers ensure efficient thermal and energy performance by removing the heat generated by active equipment, preventing hot exhaust air entering space where it is not permitted.

The InRow solution works in conjunction with racks in aisle containment and is available to suit both CAC and HAC configurations. Warm exhaust air passes over the InRow heat exchanger matrix, either by its own velocity or being pulled through via EC centrifugal fans mounted in the CL80. Heat is rejected to fluid and chilled air is passed back into the ambient space at predetermined temperature.

Quantity

The InRow coolers can be sited within an existing data centre to work with existing computer room air-conditioning to provide additional cooling. They also reduce energy consumption and remove hot spots.

Performance Examples

Performance examples—these three examples are showing the IRC options , with differing duties attainable when regulating or changing the water temperature. Other performance duties are attainable when calculating bespoke project specific requirements.

Maximum Duty 

Our highest duties offer high performance cooling based on an Industry Standard 14/20°C (57.2/68°F) water supply/return from mechanically cooled external plant, and has the ability to offer cooling capacities of up to 74 kW per rack.

Nominal Duty 

This is a more general, workable duty with 18°C/64.4°F water inlet and covers most requirements in Europe while also maintaining a room temperature of 27°C/80.6°F or lower. Delivering performance of up to 63kW per rack.

Efficient Duty 

Taking advantage of warmer water temperature inlets of 20°C/68°F the necessity of mechanical cooling is reduced, and allows for most day free cooling. This will provide customers with higher efficiency cooling and lower running costs thus beginning to obtain a return on their investment while maximising real estate.

Technical Data

Dimensions

In Row
100 Items

Data sheet content

Inrow

4. Air flow
8535 m 3 /h
4. Configuration type
HAC
4. Cooling capacity
600W
4. Fan quantity
6
4. Monitoring function
Snmp , Modbus
4. Power consumption
230V 50Hz
4. Power of Inrow
60kw
4. Type of Inrow
Water
4. Volume fluid flow
10.67 (3.0) / 47.0 m3 /h (l/s) , 7.77 (2.2) / 34.2 m3 /h (l/s) , 4.67 (1.3) / 20.6 m3 /h (l/s
4. Water out
20℃ , 25℃ , 30℃
4. Water in
14℃ , 18℃ , 20℃

16 other products in the same category

Specifications

Inrow

4. Air flow 8535 m 3 /h
4. Configuration type HAC
4. Cooling capacity 600W
4. Fan quantity 6
4. Monitoring function Snmp, Modbus
4. Power consumption 230V 50Hz
4. Power of Inrow 60kw
4. Type of Inrow Water
4. Volume fluid flow 10.67 (3.0) / 47.0 m3 /h (l/s), 7.77 (2.2) / 34.2 m3 /h (l/s), 4.67 (1.3) / 20.6 m3 /h (l/s
4. Water out 20℃, 25℃, 30℃
4. Water in 14℃, 18℃, 20℃