ColdLogik CL80 30kw data center InRow Coolers
ColdLogik CL80 30kw data center InRow Coolers

ColdLogik CL80 30kw data center InRow Coolers

Review (0)
$14,318.00
Tax Included

ColdLogik CL80 InRow Coolers ensure efficient thermal and energy performance by removing the heat generated by active equipment, preventing hot exhaust air entering space where it is not permitted.

The InRow solution works in conjunction with racks in aisle containment and is available to suit both CAC and HAC configurations. Warm exhaust air passes over the InRow heat exchanger matrix, either by its own velocity or being pulled through via EC centrifugal fans mounted in the CL80. Heat is rejected to fluid and chilled air is passed back into the ambient space at predetermined temperature.

Quantity :
In Stock 100 Available items

The InRow coolers can be sited within an existing data centre to work with existing computer room air-conditioning to provide additional cooling. They also reduce energy consumption and remove hot spots.

Performance Examples

Performance examples—these three examples are showing the IRC options , with differing duties attainable when regulating or changing the water temperature. Other performance duties are attainable when calculating bespoke project specific requirements.

Maximum Duty 

Our highest duties offer high performance cooling based on an Industry Standard 14/20°C (57.2/68°F) water supply/return from mechanically cooled external plant, and has the ability to offer cooling capacities of up to 74 kW per rack.

Nominal Duty 

This is a more general, workable duty with 18°C/64.4°F water inlet and covers most requirements in Europe while also maintaining a room temperature of 27°C/80.6°F or lower. Delivering performance of up to 63kW per rack.

Efficient Duty 

Taking advantage of warmer water temperature inlets of 20°C/68°F the necessity of mechanical cooling is reduced, and allows for most day free cooling. This will provide customers with higher efficiency cooling and lower running costs thus beginning to obtain a return on their investment while maximising real estate.

Technical Data

Dimensions

USystems
In Row
100 Items

Data sheet

4. Monitoring function
Modbus
Snmp
4. Type of Inrow
Water
4. Power of Inrow
30kw
4. Cooling capacity
300W
4. Configuration type
HAC
4. Air flow
8535 m 3 /h
4. Water in
14℃
18℃
20℃
4. Water out
20℃
25℃
30℃
4. Volume fluid flow
4.23 (1.2) / 18.6 m3 /h (l/s
7.14 (2.0) / 31.5 m3 /h (l/s)
9.88 (2.7) / 43.5 m3 /h (l/s)
4. Power consumption
230V 50Hz
4. Fan quantity
6

Specific References

No customer reviews for the moment.

Write your review
ColdLogik CL80 30kw data center InRow Coolers
ColdLogik CL80 30kw data center InRow Coolers

ColdLogik CL80 30kw data center InRow Coolers

$14,318.00
Tax Included