This isolation transformer from the Italian brand Ortea has a capacity of 350 kVA and operates at a frequency of 50 Hz, with both input and output voltages of 400 V and is made of Copper . This isolation transformer is recognized as one of the key components in industries and data centers. It is used to isolate electrical systems from each other and to reduce the risks associated with voltage fluctuations and electrical hazards. In data centers, proper isolation can help maintain data security and prevent damage to sensitive equipment. Additionally, this transformer enhances the quality of electrical signals by reducing electrical noise and vibrations, which in turn helps improve the efficiency of cooling systems and other equipment.

Quantity

 In industrial settings, isolation transformers help prevent damage to machinery and improve the reliability of systems, especially in hazardous or industrial environments where voltage fluctuations are common. Thus, the use of these transformers not only increases safety but also contributes to the optimization of overall system performance.

Rated power: 350 kVA

Coupling/Verktor group: DZN0

Frequency: 50/60 Hz

K Factor: 20

Input voltage: 400 V

Output voltage: 415 V LOAD

Core material: M270 magnetic steel

Winding material: Copper

Electrostatic shield: Between primary & secondary,

connectedtoground

Max ambient temperature: 40 °C

Insulation class: H

Insulation level: 50

Thermal class: H

Temperature rise: 125

Max altitude: 1000 m

Environmental - climate - fire class: E1 - C1 - F0

Installation: Indoor

Protection degree: IP00

Reference Standards: EN 60076 / IEC 61558 (when applicable)

No-load current: <10%

In-rush current: 8 A

No-load losses: 1620 W

Load losses: 4020 W

Efficiency: 98.5 %

Vcc: 4

Dimensions: 1050x650x950

Weight: 1350 Kg

taps 2,5% included on primary